Quick Details
Description
- Place of Origin: Hunan, China (Mainland)
- Brand Name: HNAC
- Model Number: KYN28 KYN28A KYN61
- Name: Customized 33kV Switchgear Medium Voltage Switchgear
- Frequency: 50 HZ/60HZ
- Design: Customized
- Seismic intensity: not more than 8°C
- Protection degree: IP4X for enclosure; IP2X for doors of compartments & circuit chambers
- Main voltage range: 35KV/24KV/12KV/11KV/0.4KV
- Main cabinet type: KYN28/KYN61/GGD/XGN15/...
- Rated current: 630, 1250, 1600, 2000, 2500, 3150
- Busbar system: Single busbar, and single busbar segments
- Certificate: ISO9001
KYN61-40.5 Metal-clad withdrawable AC metal-enclosed switchgear is used for the complete distribution equipments of power plant, transformer and hydropower plant system. The device is equipped with “Five Preventions” functions.
Working voltage:26~40.5kV(50 / 60 Hz)
Max. working voltage: 40.5kV
Max. rated current: 2000A
Rated short-time withstand current,4s: 20 / 25 / 31.5kA
Rated peak withstand current : 50 / 63 / 80 kA
Steel Enclosure: IP3X
Wide x deep x high: 1400mm x 2800mm x 2600mm
KYN28-24, KYN28A-12 Metal-clad withdrawable AC metal-enclosed switchgear is used for the complete distribution equipments of power plant, transformer and hydropower plant system. The device is equipped with “Five Preventions” functions.
KYN28-24
Working voltage: 13~24kV (50 / 60 Hz)
Max. working voltage: 24kV
Rated current: 1250 / 1600 / 2000 / 2500 / 3150A*(* With enforced cooling)
Rated short-time withstand current,4s: 20 / 31.5 / 40 kA
Rated peak withstand current : 63 / 80 / 100 kA
Steel Enclosure: IP4X
Wide x deep x high: 1000mm x 1800mm x 2300mm
KYN28A-12
Working voltage: 3.6~12kV (50 / 60 Hz)
Max. working voltage: 12kV
Rated current: 630 / 1250 / 1600 / 2000 / 2500 / 3150A*(* With enforced cooling)
Rated short-time withstand current, 4s: 16 / 20 / 25 / 31.5 / 40 / 50 kA
Rated peak withstand current :40 / 50 / 63 / 80 / 100 / 125kA
Steel Enclosure: IP4X
Wide x deep x high: 800/1000mm x 1500 /1660mm x 2300mm
Ambient conditions
1, For the normal design, the altitude should be not more than 1,000m. If above 1,000m, it will design according to the altitude correction factor of the highland and manufacture as per the requirements suitable for the highland altitude.
2, The ambient air temperature ranges -35℃~+40℃, and the average temperature within 24h ≤ +35℃. If exceeding the specified time, it has to reduce the capacity according to the actual condition;
3, The relative humidity should not exceed 50% at +40℃, while at lower temperatures, larger relative humidity is acceptable, e.g. 90% at +20℃. Considering the change of temperature may sometime cause the condensation, the daily average should be less than 95% and the monthly average less than 90%;
4, The water vapour average should be ave2.2*10-3Mpa or below while the monthlyrage not larger than 1.8*10-3Mpa;
5, The gradient between installation surface and vertical plane is ≤ 5°;
6, The seismic intensity should be not more than 8 degree;
7, Frequent severe violation is acceptable;
8, No pollution is allowed to the ambient air, such as corrosive substance, flammable gas, vapour and so on.