Quick Details
Description
1.1 Wide measuring range :current 0.01A-100A,voltage:40V-480V
1.2 The measure ratio is about 2 to insure the meter has the highest accuracy in the measuring range.
1.3 Strong measuring functions: three phase four wires active energy, three phase three wires active energy, three phase three wires sine reactive energy, three phase four wire 90° reactive energy, three phase three wires 60°reactive energy.
1.4 Easy to operate: there are 5 operating buttons at the bottom of the screen, which are corresponding with the reminding symbols on the screen.
1.5 The standard meter has RS-232 communication interface, which can communicate with PC in two ways. It can transmit the measuring data to PC as well as measure automatically controlled by PC.
.jpg)
2.1 Input characteristics
2.1.1 Voltage input
Input range(V) 40—480
Input measuring range(V) 60、120、240、480
Overload Voltate(V)600
Input load ≤0.5mA(480V)
2.1.2 Current input
Input range(A) 0.01—100
Input measuring range(A)100、50、25、10、5、2.5、1、0.5、0.25、0.1、0.05、0.025
Overload current(A) 150
Input overload ≤0.2mΩ(100A—0.25A)
≤0.3Ω (0.25A—0.01A)
2.2 Output characteristics
2.2.1 Output frequency of pulse
f =C ·P/3600 (H )
f =f /10000 (H )
2.2.2 Output level:TTL level
2.2.3 pulse constant
Pulse constants table of high frequency Table 1.C (P/kwh)
|
|
100A
|
50A
|
25A
|
10A
|
5A
|
2.5A
|
|
480V
|
6.25×10
|
1.25×10
|
2.5×10
|
6.25×10
|
1.25×10
|
2.5×10
|
|
240V
|
1.25×10
|
2.5×10
|
5×10
|
1.25×10
|
2.5×10
|
5×10
|
|
120V
|
2.5×10
|
5×10
|
1×10
|
2.5×10
|
5×10
|
1×10
|
|
60V
|
5×10
|
1×10
|
2×10
|
5×10
|
1×10
|
2×10
|
|
|
1A
|
0.5A
|
0.25A
|
0.1A
|
0.05A
|
0.025A
|
|
480V
|
6.25×10
|
1.25×10
|
2.5×10
|
6.25×10
|
1.25×10
|
2.5×10
|
|
240V
|
1.25×10
|
2.5×10
|
5×10
|
1.25×10
|
2.5×10
|
5×10
|
|
120V
|
2.5×10
|
5×10
|
1×10
|
2.5×10
|
5×10
|
1×10
|
|
60V
|
5×10
|
1×10
|
2×10
|
5×10
|
1×10
|
2×10
|
Pulse constant of low frequency C =C /10000
2.3 Accuracy
2.3.1 Class :0.05 or 0.1
2.3.2 Accuracy of power measurement
Accuracy of active power measurement: 0.05%、0.1%(PF≥0.5)
Accuracy of reactive power measurement: 0.1%、0.2%(PF≥0.5)
2.3.3 Accuracy of energy measurement
Accuracy of active energy measurement:0.05%、0.1%(PF≥0.5)
Accuracy of reactive energy measurement:0.1%、0.2%(PF≥0.5)
2.4 Display
2.4.1 Items of display : three phase voltage : UL1、UL2、UL3(V)
Three phase four wires UL1、UL2、UL3 mean U 、U 、U
Three phase three wires U12、U23、U31 mean U 、U 、U
Three phase current IL1、IL2、IL3(A)
Active power:P(W)
Apparent power:S(VA)
Reactive power:Q(VA)
Power factor:Pf -1.0000—1.0000
Phase angle:θ(0°—360°)
Frequency of input signal:F(H )
2.4.2 Display digits:5 digits
2.5 Power supply: 220V±10%、50H ±5% Power consumption:About20VA
2.6 Pre-heated time: 30 min
2.7 Working circumstances :
Temperature: 5℃—40℃
Relative Humidity ≤85%
Noncorrosive gas
2.8 Outline dimensions:482mm×480mm×140mm
2.9 Net weight:About 10Kg
Yueqing Gomelong Meter Co., Ltd is a high-tech company which focus on electronic and electromechanical meter design and produce,We aim to provide sophisticated energy metering solutions tailored to each customer’s business needs.Gomelong work with ISO9001 quality management system and holding CCC, certificate, CE certificate, Export Products Quality License. Our products passed the test of Zhejiang Measuring Science Academe And Country Industrial Meter Test Center.
Our company production capacity is 1million pieces per year, having full automatically SMT machine, welding testing equipment, wave- soldering machine, full-automatically testing equipment, high temperature equipment, EMC testing equipment, which makes sure our production and quality management.
We have many qualified engineers and complete developing team; we can design for every customer according to his specification data. And offer qualified products. Gomelong team keep working hard for serve products with novelty, high quality, and competitive price.