PRODUCT OVERVIEW
DZ47LE-63 is applicable to a line of AC 50Hz/60Hz, rated voltage 230V for single pole two-wire, 2-pole or 400V for 3-pole, 3-pole 4-wire, 4-pole and rated current up to 40A. It can protectthe line and motor from overload and short circuit. It can also be used for infrequent line conver-sion and infrequent motor start. It conforms with the standards of IEC61009.
TECHNICAL PARAMETER
|
Type
|
DZ47LE-63
|
|
Pole
|
1P+N,2P
|
3P,3P+N,4P
|
|
Rated current (A)
|
6,10,16,20,25,32,40,50,63
|
|
Rated voltage (V)
|
230
|
400
|
|
Rated short circuit breaking capacity Icn(KA)
|
6-32A :6 / 40-63: 4.5
|
|
Rated residual making/breaking capacity I△m(A)
|
2000
|
|
Rated residual action current I△n(A)
|
0.03,0.05,0.1,0.3
|
|
Rated residual non-action current I△no(A)
|
0.5I△n
|
Applicable conducting wire
|
Rated current(A)
|
1-6A
|
10A
|
16,20A
|
25A
|
32A
|
40,50A
|
63A
|
|
Norminal cross section of wire mm2
|
1
|
1.5
|
2.5
|
4
|
6
|
10
|
16
|
Residual current breaking time
|
In(A)
|
I△n(A)
|
Breaking time(s) when equals to rating following
|
|
I△n
|
2I△n
|
5I△n
|
5,10,20,50,100,200,500a(A)
|
I△tb
|
|
6-63
|
0.03, 0.05, 0.1, 0.3
|
0.1
|
0.06
|
0.04
|
0.04
|
0.04
|
The over-current protection property
|
Ambient Temperature
|
Initial Status
|
Test Current
|
Expected Result
|
Expected Result
|
Note
|
|
30±oC
|
Cold position
|
1.13In
|
t≥1h
|
Non-release
|
-
|
|
Carried out immediately after previous test
|
1.45In
|
t< 1h
|
Release
|
-
|
|
Cold position
|
2.55In
|
1s < T < 60S(IN≤32A)
|
Release
|
Current smoothly rises tospecified value within 5s
|
|
Cold position
|
2.55In
|
1s < T < 120S(IN>32A)
|
Release
|
|
-5~+40oC
|
Cold position
|
3In
|
t≥0.1s
|
Non-release
|
Type B
|
|
Cold position
|
5In
|
t<0.1s
|
Release
|
Type B
|
|
Cold position
|
5In
|
t ≥ 0.1s
|
Non-release
|
Type C
|
|
Cold position
|
10In
|
t < 0.1s
|
Release
|
Type C
|
|
Cold position
|
10In
|
t≥0.1s
|
Non-release
|
Type D
|
|
Cold position
|
20In
|
t<0.1s
|
Release
|
Type D
|